Control Valve

  • R2..AC/R6..AO 2-way Open/Close Ball Valves
  • DN15...150
  • Shut-off function and 2-point control
  • in cold and hot water circuits
  • Applications
  • For shutting off cold and hot water circuits in heating and ventilation
  • systems on the water side or for 2-point control of these circuits.
Data Sheet

  • R2..AC 2-way Characterised Control Valves DN15...50
  • Equal percentage characteristics for modulating control of cold and hot water
  • Application : water-side control of air handling units in air conditioning systems
  • water-side control in heating systems
Flow medium : Cold and hot water, water with max.50% volume of Glycol
Temp. of medium : -5...+100C
Rated pressure : 2500kPa
Flow characteristic : Equal percentage
Pipe connector : Internal thread to ISO 7/1
Data Sheet

  • R6..AO 2-way Characterised Control Valves DN65...150
  • Equal percentage characteristics for modulating control of cold and hot water
  • Application : water-side control of air handling units in air conditioning systems http://www.cartier-replica.us/
  • water-side control in heating systems
Flow medium : Cold and hot water, water with max.50% volume of Glycol
Temp. of medium : -5...+100C
Rated pressure : 1600kPa
Flow characteristic : Equal percentage
Pipe connector : Flanged ISO 7005-2, PN16
Data Sheet

  • R3..AC 3-way Open/Close mixing Ball Valves
  • DN15...50
  • Change-over function and 2-point control
  • in cold and hot water circuits
  • Applications
  • For changing over cold and hot water circuits in heating
  • and ventilation systems on the water side or for 2-point
  • control of these circuits.
Data Sheet

  • R3..AC 3-way Characterised Control Valves DN10...50 with internal thread
  • For open and closed cold and warm water systems
  • For modulating control on the water side of air handling and heat systems http://www.quickdownpdf.com/
  • air-bubble-tight (control path A-AB)
Flow medium : Cold and hot water, water with max.50% volume of Glycol
Temp. of medium : +5...+110C (lower or higher temperatures on request)
Pipe connector : Pipe connector : Internal thread to ISO 7/1
Data Sheet

  • TR.. General Rotary Actuators :
  • for 2-way DN15...25 CCV
  • for 3-way DN15...20 CCV
  • Torque: 2Nm
  • Modulating control: TR24-SR (AC/DC 24V)
  • Open/Close or 3-point:
  • TR24 (AC/DC 24V)
  • TR230-3 (AC 230V 50Hz)
Data Sheet
Installation Manuel
Dimensions

  • LRU.. General Rotary Actuators for:
  • for 2-way DN32...40 CCV
  • for 3-way DN25...32 CCV
  • Torque: 5Nm
  • Modulating control: LRU24-SR (AC/DC 24V)
  • Open/Close or 3-point control:
  • LRU24(-S) (AC/DC 24V)
  • LRU230(-S) (AC 100...240V)
Data Sheet
Installation Manuel
Dimensions

  • NRU.. General Rotary Actuators :
  • for 2-way DN50 CCV
  • for 3-way DN32...50 CCV
  • Torque: 10Nm
  • Modulating control: NRU24-SR (AC/DC 24V)
  • Open/Close or 3-point:
  • NRU24(-S) (AC/DC 24V)
  • NRU230(-S) (AC 100...240V)
Data Sheet
Installation Manuel
Dimensions

  • SRVU..-5 General Rotary Actuators for:
  • DN65...80 CCV
  • Torque: 20Nm
  • Modulating control: SRVU24-SR-5 (AC/DC 24V)
  • Open/Close or 3-point control:
  • SRVU24(-S)-5 (AC/DC 24V)
  • SRVU230(-S)-5 (AC 100...240V)
Data Sheet
Installation Manuel
Dimensions

  • GRVU..-7 General Rotary Actuators for:
  • DN100...150 CCV
  • Torque: 40Nm
  • Modulating control: GRU24-SR-7 (AC/DC 24V)
  • Open/Close control:
  • GRVU24-7 (AC/DC 24V) http://www.popdf.com/
  • GRVU230-7 (AC 100...240V)
Data Sheet
Installation Manuel
Dimensions

  • TRF.. Mech.Fail-Safe Rotary Actuators :
  • for 2-way DN15...25 CCV
  • for 3-way DN15...20 CCV
  • Torque: 2Nm
  • Modulating control: TRF24-SR (AC/DC 24V)
  • 3-point control: TRF24-2 (AC/DC 24V)
  • Open/Close control:
  • TRF24(-S) (AC/DC 24V)
  • TRF230(-S) (AC 100...240V)
Data Sheet
Installation Manuel

  • L(R)F.. Mech. Fail-Safe Rotary Actuators :
  • for 2-way DN32...40 CCV
  • for 3-way DN25...32 CCV
  • Torque: 4Nm http://www.popwc.co.uk/
  • http://Swim-Watch.co.uk/
  • Modulating control: L(R)F24-SR (AC/DC 24V)
  • 3-point control: LF24-3 (AC/DC 24V)
  • Open/Close control:
  • LRF24(-S) (AC/DC 24V)
  • LRF230(-S) (AC 230V)
Data Sheet
Installation Manuel

  • NRFU.. Mech. Fail-Safe Rotary Actuators
  • for 2-way DN50 CCV
  • for 3-way DN32...50 CCV
  • Torque: 10 Nm
  • Modulating control: NRFU24-SR (AC/DC 24V)
  • Open/Close control:
  • NRFU,NRFU-S2 (AC 24...240V/DC 24...125V)
Data Sheet
Installation Manuel

  • SRFU..-5 Mech. Fail-Safe Rotary Actuators for operation of: DN65...80 CCV
  • Torque: 20Nm
  • Modulating control: SRFU24-SR-5 (AC/DC 24V)
  • Open/Close control:
  • SRFU-5, SRFU-S2-5 (AC 24 ...240V/DC 24 ...125V)
Data Sheet
Installation Manuel

  • GRKU..-7 Electronic Fail-Safe Rotary Actuators
  • For operation : DN100...150 CCV
  • Torque: 40Nm
  • Open/Close control:GRKU24-7 (AC/DC 24V)
  • Modulating control: GRKU24-MF-7 (AC/DC)
Data Sheet
Installation Manuel

  • LRQU.. Fast Running Rotary Actuators
  • for 2-way DN15...40 CCV
  • for 3-way DN15...32 CCV
  • Torque: 4Nm
  • Modulating control: LRQU24-SR (AC/DC 24V)
  • Open/Close control: LRQU24 (AC/DC 24V)
Data Sheet
Installation Manuel

  • NRQU.. Fast Running Rotary Actuators
  • for 2-way DN50 CCV
  • for 3-way DN32...40 CCV
  • Torque: 8Nm
  • Open/Close control: NRQU24 (AC/DC 24V)
  • Modulating control: NRQU24-SR (AC/DC 24V)
Data Sheet
Installation Manuel

  • Weathershield ZS-.. for : ZS-NR DN50, NR.. series actuators
  • ZS-SR DN65...80, SR..series actuators
  • ZS-GR DN100...150, GR..series actuators
Data Sheet
Installation Manuel