Service | : | Air and noncombustible, compatible gases. |
Temperature Limits | : | Process ambient temperature from -4 to 185˚F (-20 to 85˚C). |
Pressure Limits | : | Max. Operating Pressure: 40” W.C. (10 kPa) for all pressure ranges |
Switch Type | : | Single-pole double-throw (SPDT) |
Electrical Rating | : | Standard: Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; Gold Contact Option: 0.4 A/ 250 VA |
Service | : | Air and non-combustible, compatible gases |
Accuracy | : | ±1% for 0.25˝ (50 Pa), 0.5˝ (100 Pa), 2˝ (500 Pa), 5˝ (1250 Pa), 10˝ (2 kPa), 15˝ (3 kPa), 25˝ (5 kP |
Temperature Limits | : | 0 to 150°F (-18 to 66°C) |
Pressure Limits | : | 1 psi maximum, operation; 10 psi, burst |
Power Requirements | : | 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire) |
Output Signals | : | 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire) |
Display (optional) | : | 4 digit LCD |
Service | : | Compatible gases and liquids |
Temp. limits | : | 30 to 140°F (-1 to 60°C) |
Pressure Limits | : | 200 psig (13.8 bar) |
Switch Type | : | SPDT snap switch |
Enclosure Rating | : | Weatherproof UL type 4X (IP65) |
Service | : | Air and non-combustible, compatible gases |
Accuracy | : | ±1.5% for 0.25˝ and ±0.25˝ w.c. ranges. Ranges 0.5˝ to 5˝ w.c. and corresponding bi-directional (exc |
Pressure LImits | : | Ranges ≤ 2.5 in w.c.: 25 psi; ±2.5˝, 5 in w.c.: 5 psi; 10 in w.c.: 5 psi; 25 in w.c.: 5 psi; 50 in w |
Temperature Limits | : | 32 to 140°F (0 to 60°C) |
Power Requirements | : | 12-28 VDC, 12-28 VAC 50 to 400 Hz. |
Output Signal | : | 4-20 mA DC into 900 ohms max. |
Display | : | Backlit 4 digit LCD 0.4˝ height LED indicators for set point and alarm status |
Service | : | Air and non-combustible, compatible gases. |
Temperature Limits | : | 30 to 180°F (-34 to 82.2°C); Case: -58 to 140°F (-50 to 60°C) |
Pressure Limits | : | 45 in w.c. (11.2 kPa) continuous, 10 psig (68.95 kPa) surge |
Switch Type | : | SPDT |
Electrical Rating | : | 15 A @ 120 to 480 VAC, 60 Hz. Resistive 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz |
Service | : | Compatible gases & liquids |
Wetted Materials | : | Types 316, 316L SS |
Accuracy | : | +/- 0.5% F.S. (includes linearity, hysteresis & repeatability) |
Temperature Limits | : | 0 to 200°F (-18 to 93°C) |
Pressure Limits | : | See chart |
Power Requirements | : | 13-30VDC |
Output Signal | : | 4 to 20 mA. Optional 0-5, 1-5, 0-10, 1-6 or 2-10 VDC |